1. What are the
components of the Active System? What does Summit Hill Laboratories
supply? What do I supply?
The VETROSON® ACTIVE
ANESTHESIA SCAVENGER consists of:
The above are supplied by
Summit Hill Laboratories.
The practice supplies
1-1/2” SCH 40 PVC plastic pipe which connects the 1-l/2” SCH 40 Male Hose
Connector Fitting at the end of the 6’ flexible heavy hose of the Power Unit to
the “Y” Tee Fitting which, in turn, connects with the end of the 30mm
Scavenging Interface. This material is inexpensive and readily available
through any plumbing or building material contractor.
The practice also supplies
additional Scavenging Interfaces, “Y” Tee Fittings and Carrier Air Inlet
Valves if indicated. Please refer to Questions 5, 11 &
14.
Please refer to Page 2 of
the OPERATING INSTRUCTIONS for a diagram showing how the above system is
connected.
2. Can I install
the system or do I need a contractor?
A 4-1/4” diameter hole
must be cut through the wall where the Power Unit is mounted and the PVC
plastic pipe must be routed wherever indicated – usually above a drop
ceiling. The OPERATING INSTRUCTIONS clearly illustrate how this is
done. Some veterinarians install the system, while others use a
contractor depending upon each veterinarian’s skills and available
time.
3. I am in a
shopping center and my O.R. is in the middle office. I do not have an
outside wall in the O.R. How can I hook up the
system?
The Power Unit may be
installed on any outside wall, usually in the rear room in the case of a
shopping center practice. An “On/Off” remote switch with a light would
then be mounted in the O.R. and connected to the Power Unit with electrical
wires.
4. May I mount
the Power Unit in a closet or attic? If so, how long a 4” vent pipe may
be used?
Yes, just make sure the
vent pipe is no longer than 20’, has no more than two 90-degree elbows and
that the exhaust port is adequately protected from the elements. We
supply a 10” section. Longer lengths may be purchased at any home supply
center.
5. How many “dead
ends” may I have in the system?
You may have as many as
indicated. Page 7 of the OPERATING INSTRUCTIONS shows several layouts.
Remember a Carrier Air Inlet Valve must be inserted at each “dead
end”.
6. I cannot use
straight 1-1/2” PVC pipes in my ceiling. Because of beams I cannot get a
straight pass. May I use corrugated tubing?
Yes. Corrugated
tubing may be used to go around beams. Do not employ sharp
angles.
7. I cannot install
the piping over the ceiling. May I install the piping under the
floor?
Yes, the piping may be
installed under the floor or along the wall if ceiling positioning is not
practical.
8. Must I have an
electric outlet nearby?
We supply a 6’ electrical
cord. If the outlet is more than 6” from the installation point, a
grounded extension cord should be used.
9. Are there fuses
to replace?
The Power Unit has one 1-l/4AMP fuse located above
the “On/Off” switch.
10. May I mount the
Power Unit upside down or on its side?
Yes. If the Power
Unit is mounted “upside down”, the faceplate may be unscrewed and
reversed.
11. I have one
anesthesia machine and use it in the surgery room, dental area and in the
X-ray department. How many interfaces do I
need?
Three. (Two
additional) An Interface must be in position to accept the
anesthesia machine whenever the machine is moved to that work area.
Interfaces are permanently cemented into the “Y” Tee Piece and
do not function until affixed to the nipple of the Scavenging Pop-Off
Valve.
12. Will scavengers
fit any manufacturer’s machine?
Yes, as long as it has a
Scavenging Pop-Off Valve.
13. How can I
connect a Scavenger Interface to an old anesthesia machine that does not have
a scavenging Pop-Off Valve?
Replace your old Pop-Off
Valve with a new VETROSON®. The following seven models of the
VETROSON® Pop-Off Valves are available for the listed small animal veterinary
anesthesia machines:
#SPA1000 for Summit Hill & Snyder Machines (This valve cannot be retrofitted in the field)
#SPA1100 for Ohio, bickford and Pitman Moore 960, 970 & 980 Machines
#SPA1300 for Drager Machines
#SPA1400 for Dupaco Machines
#SPA1500 for Foregger Machines
#SPA1805 for Ohio
Heidebring Machines
If your practice has a
“human” anesthesia machine – and none of the above Pop-Off Valves match – send
your Pop-Off valve to Summit Hill Laboratories and we will see if we have a
threaded adapter which will compare with yours.
14. How many
machines can I connect with the VETROSON® Active Anesthesia Scavenger
System? How many feet apart can they be?
We have successfully
connected 25 anesthesia machines with our system using up to 200’ of PVC
piping. Remember an additional Scavenging Interface and “Y” Tee Piece
will be required for the second, third, fourth, etc anesthesia machine or
machine location.
15. With a 100
C.F.M. pull from the Power Unit, why doesn’t this pull my Pop-Off Valve
down?
We have three valve
positions in the Active system which adjust for air pressure and the animal’s
breathing.
16. How noisy is
the Active?
The unit is barely
audible when
running.
17. Must the
scavenger system be “tight”?
To remove all true gases
from the environment to the outside, the entire scavenger system, as well as
the anesthesia machine itself, must have no leaks. The scavenger system
is completely sealed from the Scavenging Pop-Off Valve to the outside.
The practice must double check the anesthesia machine for leaks and correct
any if they occur. Endotracheal tubes also should be checked for the
proper fit.
18. Is there any
(maintenance) service required after installation?
The motor/blower assembly is sealed and self-lubricating and requires no service. However, check the three valves in the “criss-cross” (where the 30mm and 19mm hoses are joined).
Animal hair and debris
may enter these ports causing inflation or depression of the breathing bag
depending in which valve the blockage is.
19. Can I add on
the system in the future?
Yes. Cut into the
PVC piping, add a “T” or any other fitting indicated, and lay more piping to
the desired location, add a “Y” Tee Fitting, Scavenging Interface and
Carrier Air-Inlet Valve if indicated.
20. What can the problem
be if the bag on the anesthesia machine over inflates, or if the bag is
completely deflated?
FIRST LOOK FOR PROBLEMS
RELATED TO THE ANESTHESIA MACHINE. This is where most of the problems will be
– especially on a recently installed VETROSON® Active Anesthesia Scagenger
System.
Unhook the Scavenger Interface from the pop-off valve on the anesthesia machine. If this corrects the problem, we must look to the scavenging system for the cause. If it doesn’t,
checkout the problem as
follows:
Note: some bags will appear to be fuller than others because of the tensile strength of the latex or rubber compound used in the making of the bag. Use the pressure gauge to
determine the fullness of
the bag.
IF THE PROBLEM IS NOT THE ANESTHESIA MACHINE AND
THE BAG ON THE ANESTHESIA MACHINE IS DEFLATED, PROCEED AS
FOLLOWS:
The two side valves may be visually inspected. If clogged with hair, remove using
tweezers.
IF THE PROBLEM IS NOT THE
ANESTHESIA MACHINE AND THE BAG ON THE ANESTHESIA MACHINE OVER INFLATES,
PROCEED AS FOLLOWS:
a) One valve is hidden in the “criss-cross” at the end of the 19mm hose. Blockage here
would cause the bag to over inflate. To check it disconnect the interface from the
anesthesia machine’s pop-off valve and blow into the 19mm hose to determine if there is
partial or complete valve blockage. This valve in the “criss-cross” may become
clogged with hair or other debris. If it is clogged, disconnect the 19mm hose from the
“criss-cross” and clean out the internal valve using tweezers. The hose may
easily be re-positioned with minimal pressure.
is clogged, the result will be an inflated bag. To correct this disconnect the 30mm hose
from the valve, remove the debris from
the inlet hole and replace the 30mm hose.
If there is no blockage in
the valve system, then the problem definitely lies with the anesthesia machine.
Re-check the points listed above.
Although very unlikely to happen, if a strong air current (such as exhaust from an A/C unit) blows into the exhaust vent, the bag would over inflate.
21. What are the benefits of
having a VETROSON® ACTIVE ANESTHESIA SCAVENGER?
22. When would a
VETROSON® Passive Anesthesia Scavenger be indicated?
A passive system is
indicated when only one or two anesthesia machine locations are
used. If more than two locations are used – or if the practice plans to
add another anesthesia machine or two, the active system is more
economical.
23. Must I specify
the thickness of the wall for using a passive system?
The thru-the-wall vent
assembly is designed to fit walls up to 12”. If the practice has a
thicker wall, a special order should be placed for a longer vent
assembly. Please note that the vent assembly must be located below the
level of the pop-off valve as gravity is employed and the gases must flow
downward from the anesthesia machine.
24. How far from
the outside wall can a passive system be employed?
Our exhalation tubing is
9’ long. Therefore, the anesthesia machine must be used within 9’ of the
outside wall.
25. In what
circumstances shouldn’t a passive system be used?
Since the passive system is dependent upon gravity, it cannot be used in a basement situation where the outside level is above the anesthesia machine; it cannot be used where the operation room is in an “inside” location as more than 9’ for exhalation tubing would have to
be used. In the above two situations our Active System would have to be employed.